ASTM E2231表面燃燒特性評(píng)估用管和管絕緣材料的樣品制備和安裝的標(biāo)準(zhǔn)規(guī)范

放大字體  縮小字體 發(fā)布日期:2012-02-08   瀏覽次數(shù):215  分享到: 分享到騰訊微博
ASTM E2231表面燃燒特性評(píng)估用管和管絕緣材料的樣品制備和安裝的標(biāo)準(zhǔn)規(guī)范
ASTM E2231 Standard Practice for Specimen Preparation and Mounting of Pipe and Duct Insulation Materials to Assess Surface Burning Characteristics
ASTM E2231表面燃燒特性評(píng)估用管和管絕緣材料的樣品制備和安裝的標(biāo)準(zhǔn)規(guī)范
Pipe and duct insulation systems are often evaluated with Test Method E84 to comply with building or mechanical code requirements. This practice describes, in detail, specimen preparation and mounting procedures for single-component pipe or duct insulation systems and for multi-component pipe or duct insulation systems.
The material, system, composite, or assembly tested shall be representative of the completed insulation system used in actual field installations, in terms of the components, including their respective thicknesses.
Pipe and duct insulation systems consist of a variety of materials and constructions.
Some testing laboratories have developed a number of protocols for testing pipe or duct insulation systems which utilize one generic type of materials, all of them with an insulation core and a jacket. Those protocols are the origin of this practice, which makes them generic, to reduce material bias in the standard; they have resulted in the procedures presented in 6.1. The procedures presented in 6.2-6.5 address other types of pipe or duct insulation systems.
This practice addresses specimen preparation and mounting of systems of the types described in 5.5.1-5.5.3 and testing of supplementary materials as described in 5.6.
Multi-component systems containing an insulation core and a jacket, with or without adhesive between insulation core and jacket, not intended to be bonded to a pipe or duct substrate. Specimen preparation and mounting for such systems is described in 6.1 if they are self-supporting and in 6.2 if they are not self-supporting.
Single component systems, not intended to be bonded to a pipe or duct substrate. Specimen preparation and mounting for such systems is described in 6.3 if they are self-supporting and in 6.4 if they are not self-supporting.
Systems intended to be bonded to a pipe or duct substrate. Specimen preparation and mounting for such systems is described in 6.5.
Reflective insulation materials (see 3.2.10 and 3.2.11) shall be tested using the procedures for specimen preparation and mounting described in Practice E2599.
Specimen preparation and mounting procedures for systems not described in this practice shall be added as the information becomes available.
Supplementary Materials:
It is recognized that supplementary materials for pipe or duct insulation systems are normally able to generate heat, flame or smoke. Thus, the fire safety of the entire system depends, at least to some extent, on the fire performance of supplementary materials. Consequently, the fire-test-response characteristics of all supplementary materials shall be assessed to obtain a full assessment of the fire-test-response of the pipe or duct insulation system. See Appendix X1.
Supplementary materials are often present intermittently spaced, and not for an extended length, in a pipe or duct insulation system. Thus, it is not always possible to suitably test them in conjunction with a pipe or duct insulation system.
Testing of Supplementary Materials—Supplementary materials that have not been fully tested in conjunction with the pipe or duct insulation system, in accordance with Section 6, shall be tested for flame spread and smoke development as single-component systems, in accordance with Test Method E84.
The limitations for this procedure are those associated with Test Method E84.
1. Scope
1.1 This practice describes procedures for specimen preparation and mounting when testing pipe and duct insulation materials to assess flame spread and smoke development as surface burning characteristics using Test Method E84.
1.2 If the pipe or duct insulation materials to be tested are reflective insulation materials (see 3.2.10 and 3.2.11), the materials shall be tested using the procedures for specimen preparation and mounting described in Practice E2599 and not the procedures described in 6.1 through 6.6.
1.3 Testing is conducted with Test Method E84.
1.4 This practice does not provide pass/fail criteria that can be used as a regulatory tool.
1.5 Use the values stated in inch-pound units as the standard, in referee decisions. The values in the SI system of units are given in parentheses, for information only; see for further details.
1.6 This fire standard cannot be used to provide quantitative measures.
1.7 Fire testing of products and materials is inherently hazardous, and adequate safeguards for personnel and property shall be employed in conducting these tests. Fire testing involves hazardous materials, operations, and equipment. This standard gives instructions on specimen preparation and mounting, but the fire-test-response method is given in Test Method E84. See also Section 8.
1.8 The text of this standard references notes and footnotes which provide explanatory material. These notes and footnotes (excluding those in tables and figures) shall not be considered requirements of the standard.
1.9 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.
1.10 This fire standard cannot be used to provide quantitative measures.

2. Referenced Documents (purchase separately)
ASTM Standards
C168 Terminology Relating to Thermal Insulation
C1186 Specification for Flat Fiber-Cement Sheets
C1224 Specification for Reflective Insulation for Building Applications
C1396/C1396M Specification for Gypsum Board
E84 Test Method for Surface Burning Characteristics of Building Materials
E136 Test Method for Behavior of Materials in a Vertical Tube Furnace at 750C
E176 Terminology of Fire Standards
E2599 Practice for Specimen Preparation and Mounting of Reflective Insulation Materials and Radiant Barrier Materials for Building Applications to Assess Surface Burning Characteristics
UL Standards
UL181 Standard for Safety for Factory-Made Air Ducts and Connectors
Index Terms
Ducts/duct liners--specifications; Flame spread; Pipe thermal insulation; Smoke analysis; Specimen preparation (general); Surface burning characteristics;



  詳情請(qǐng)咨詢
  防火資源網(wǎng)-阻燃防火測(cè)試中心
  電話:(+86)0592-5056213
  傳真:(+86)0592-5105807
  郵件:firetest@firetc.com

凡注明"防火資源網(wǎng)"的所有作品,由<防火資源網(wǎng)>整理編輯,任何組織未經(jīng)<防火資源網(wǎng)>及其擁有者授權(quán),不得復(fù)制、轉(zhuǎn)載、摘編或利用其它方式應(yīng)用于任何商業(yè)行為。

 
 
[ 防火測(cè)試中心搜索 ]  [ ]  [ 告訴好友 ]  [ 打印本文 ]  [ 關(guān)閉窗口 ]  [ 返回頂部 ]

 

 
 
推薦防火測(cè)試
推薦圖文
點(diǎn)擊排行
 
 
網(wǎng)站首頁(yè) | 廣告服務(wù) | 關(guān)于我們 | 聯(lián)系方式 | 服務(wù)協(xié)議 | 版權(quán)聲明 | 網(wǎng)站地圖 | 友情鏈接 | 網(wǎng)站留言 | 舊版本 | 閩ICP備09009213號(hào)
?2019-2021 FIRETC.COM All Rights Reserved ? 備案號(hào):閩ICP備09009213號(hào)-1在線客服 點(diǎn)擊QQ交談/留言 點(diǎn)擊QQ交談/留言
主站蜘蛛池模板: 人妻精品少妇二区 | 性一交一伦一乱一A片 | 久久精品国产99久久久 | 国产欧美日韩精品丝袜高跟鞋 | 久久人妻AV一区二区软件 | 欧美色欧美亚洲另类二区 | 国产成年无码AⅤ片在线观看 | 亚洲精品综合欧美一区二区三区 | 亚洲中文字幕成人无码 | 亚洲欧洲精品成人久久 | 亚洲东京热av一区二区 | 香港三级日本三级a视频 | 四虎国产精品免费久久 | 亚洲女线av影视宅男宅女天堂 | 国产一区二区三区亚洲欧美 | 成人国产亚洲欧美一区 | 国产成人亚洲综合无码精品 | 无码国产精品一区二区免 | 欧美国产另类首页 | 国产激情视频在线观看的 | 国产精品久久欧美一区 | 亚洲av怡红院影院怡春院 | 国产精品v片在线观看 | 中出在线观看 | 精品水蜜桃久久久久久久 | 国产午夜福利久久精品 | 国产成人久久 | 亚洲av永久无码精品播放在线 | 亚洲午夜久久久久久尤物 | 精品欧洲无码av一区二区 | 亚洲日韩欧美一区二区三区在线 | 国产精品欧美韩国日本久久 | 国产在线乱码一区二区三区 | 日本一本免费一二区 | 尤物蜜芽福利国产污在线观看 | 99久久做夜夜爱天天做精品 | 日本高清不卡码无码v亚洲 日本高清免费一本视频在线观看 | 国产在线高清一级毛片 | 日日碰狠狠添天天爽 | 国产成人无码精品久久小说 | 国产成人久久综合一区77 |